Solutions to common failures of wall-hung boiler water pumps
- Author:
- Origin:
- Time of issue:2021-02-23 13:40
- Views:
(Summary description)a) Unscrew the slotted copper screw on the end of the water pump, exhaust the air of the water pump, and restart.
b) If the heating system distributor is not opened, open the distributor; if the filter is clogged, remove the filter, rinse it, and install it, make up water and exhaust, and restart.
c) If there is air in the pipe and it is not exhausted, exhaust the air and restart.
d) If the water flow switch fails, use a multimeter to detect whether there is a switch signal output during operation. If there is a signal output, that is, the water flow switch is turned on, it may be that the connector is not well connected or the wire is disconnected, then plug the connector or replace the wire; if the wire and the connector are intact, the controller is faulty, replace the controller . If there is no signal output, it means that the water flow switch is stuck or the waterway is blocked; if the water flow switch is stuck, remove the water flow switch to rinse and reinstall; and replenish water. Exhaust and restart again; waterway blockage is handled according to method b.
e) Install a distributor (switch) at the heating water outlet, and turn off the distributor a bit smaller.
Fan pressure failure
①Fault phenomenon: if the fan does not run or runs slowly, the controller will give an alarm, and the display will show the fan air pressure fault code.
Causes of failure: a) The fan is stuck or burned out; b) The connector is in poor contact; c) The controller is faulty, d) The capacitor is damaged, and e) The mains voltage is too low.
Solution: a) Check the fan with a multimeter, replace the fan when the circuit breaks, or replace the fan if it is stuck. b) The connector is in poor contact and reconnect it. c) If the controller fails, replace the controller. d) If the fan impeller can be started by pulling it by hand, the capacitor is damaged. Replace the capacitor. e) Install a voltage regulator to increase the mains voltage to 220V.
②Fault phenomenon: the fan is running normally, the controller does not ignite, the main controller gives an alarm, and the display shows the fault code as fan air pressure failure.
The cause of the failure: a) the wind pressure switch is short-circuited, b) the wind pressure switch is not closed. c) Poor contact of the connector. d) The suction and exhaust ports are blocked. e) The controller is faulty.
Solution: a) Check with a multimeter. If the wind pressure switch is closed before the fan starts, replace the work or adjust the wind pressure switch. b) If it is normal before the fan is started, but does not close after the fan is started, the air pressure switch can be adjusted. If the problem cannot be solved after the adjustment, replace the air pressure switch. ; Also check whether the venturi tube or the wind pressure tube is blocked. c) If the connector is in poor contact, reconnect it. d) If all the previous faults are eliminated, check whether the suction and exhaust are smooth or blocked; if the suction and exhaust are not smooth, clean the flue; if it is blocked, clean it. e) The faults of a, b, c, d have been eliminated, then check whether the pulse igniter connector is in contact
Solutions to common failures of wall-hung boiler water pumps
(Summary description)a) Unscrew the slotted copper screw on the end of the water pump, exhaust the air of the water pump, and restart.
b) If the heating system distributor is not opened, open the distributor; if the filter is clogged, remove the filter, rinse it, and install it, make up water and exhaust, and restart.
c) If there is air in the pipe and it is not exhausted, exhaust the air and restart.
d) If the water flow switch fails, use a multimeter to detect whether there is a switch signal output during operation. If there is a signal output, that is, the water flow switch is turned on, it may be that the connector is not well connected or the wire is disconnected, then plug the connector or replace the wire; if the wire and the connector are intact, the controller is faulty, replace the controller . If there is no signal output, it means that the water flow switch is stuck or the waterway is blocked; if the water flow switch is stuck, remove the water flow switch to rinse and reinstall; and replenish water. Exhaust and restart again; waterway blockage is handled according to method b.
e) Install a distributor (switch) at the heating water outlet, and turn off the distributor a bit smaller.
Fan pressure failure
①Fault phenomenon: if the fan does not run or runs slowly, the controller will give an alarm, and the display will show the fan air pressure fault code.
Causes of failure: a) The fan is stuck or burned out; b) The connector is in poor contact; c) The controller is faulty, d) The capacitor is damaged, and e) The mains voltage is too low.
Solution: a) Check the fan with a multimeter, replace the fan when the circuit breaks, or replace the fan if it is stuck. b) The connector is in poor contact and reconnect it. c) If the controller fails, replace the controller. d) If the fan impeller can be started by pulling it by hand, the capacitor is damaged. Replace the capacitor. e) Install a voltage regulator to increase the mains voltage to 220V.
②Fault phenomenon: the fan is running normally, the controller does not ignite, the main controller gives an alarm, and the display shows the fault code as fan air pressure failure.
The cause of the failure: a) the wind pressure switch is short-circuited, b) the wind pressure switch is not closed. c) Poor contact of the connector. d) The suction and exhaust ports are blocked. e) The controller is faulty.
Solution: a) Check with a multimeter. If the wind pressure switch is closed before the fan starts, replace the work or adjust the wind pressure switch. b) If it is normal before the fan is started, but does not close after the fan is started, the air pressure switch can be adjusted. If the problem cannot be solved after the adjustment, replace the air pressure switch. ; Also check whether the venturi tube or the wind pressure tube is blocked. c) If the connector is in poor contact, reconnect it. d) If all the previous faults are eliminated, check whether the suction and exhaust are smooth or blocked; if the suction and exhaust are not smooth, clean the flue; if it is blocked, clean it. e) The faults of a, b, c, d have been eliminated, then check whether the pulse igniter connector is in contact
- Categories:News
- Author:
- Origin:
- Time of issue:2021-02-23 13:40
- Views:0
Scan the QR code to read on your phone
最新资讯
Contact us
Tel:0576-8633 3332 180 0586 0399
E-mail:jcamerica@chinajingchuan.com
Url:www.jcpbg.com
Add:Shuangling Industrial Zone, Daxi Town, Wenling City, Zhejiang Province
Copyright © Zhejiang Jingchuan Pump Technology Co.,Ltd. All Rights Reserved 浙ICP备2021013253号 Powered by 300.cn